Cable Tray Sizing & Load Calculator
Enter your NYY or CV cables, choose the tray type, and get a reference tray width from the EIT วสท. 022001-22 §5.15 fill check, a suggested height, and the cable load in kg/m. Free, runs entirely in your browser.
Free · no sign-up · calculated in your browser
3. Result
Method and data sources
Sizing method
Default method: EIT วสท. 022001-22 §5.15 (cable trays). Table 5-7 and Table 5-8 values used here were taken from a Naresuan University lecture (Lesson 7.2 Cable Tray) that quotes those tables, and were cross-checked against the lecture’s worked examples. The official วสท. 022001-22 book was not available (paid publication), so these numbers are not read from the book itself. Please compare with the official book before relying on them. No table rows are invented for widths other than 150, 300, 450, 600, 750 and 900 mm.
Rules implemented
- Multicore, all ≥ 95 mm² (5.15.4): single layer; ladder / ventilated: ΣOD ≤ width; solid bottom: ΣOD ≤ 0.9 × width.
- Multicore, all < 95 mm²: Σ qty × π(d/2)² ≤ Table 5-7 column 1 (ladder / ventilated) or column 3 (solid bottom).
- Multicore, mixed: large cables single layer with nothing on top; small-cable area ≤ column 2 (X − 30.5·Sd) or column 4 (X − 25.4·Sd), X = column 1 / 3 value of that width, Sd = ΣOD of the ≥ 95 mm² cables.
- Single-core: 50–95 mm² and ≥ 400 mm²: ΣOD ≤ width; 120–300 mm²: Table 5-8 (column 1; mixed: X − 27.9·Sd). Solid-bottom single-core has no วสท. provision (flagged). Other sizes: conservative ΣOD (flagged).
- Spare m (%): effective area = actual area × (1 + m); effective ΣOD = actual ΣOD × (1 + m); needed X = (area + k·Sd) × (1 + m).
- Height (practice): smallest YC height ≥ largest OD + 10 mm.
- Load: Σ qty × kg/m (+ your tray self-weight); per support = kg/m × spacing.
Cable data
Outer diameter and weight come only from the built-in library: NYY – Thai Yazaki NYY catalog (OD = maximum overall diameter in TIS 11 Part 101-2559, weights approximate kg/km); CV – Thai Yazaki FD-0.6/1kV-CV catalog (approximate OD and kg/km). NYY 2-core 16, 25 and 35 mm² weights were inconsistent in the catalog and are left empty – enter them yourself. Real cables vary by maker; edit OD / weight or use a custom cable for your product.
YC catalog sizes
Widths 100–600 mm in 50 mm steps; heights 50, 75, 100, 150 and 200 mm (YC CAD model range; the same grid is used for ladder). 750 / 900 mm are Table 5-7 widths but are not in the YC catalog – for those, send an inquiry for a custom tray. Nominal width is not the same as the inside width.
About the 40 % / 50 % “rule”
Many people quote “40 % power / 50 % control”. Under NEC 392.22 the 50 % (ladder / ventilated) and 40 % (solid) fill percentages apply only to trays carrying control and/or signal cables alone, with usable depth capped at 150 mm. Power and lighting cables use a Table area limit or a single-layer diameter sum. That is why this tool uses วสท. §5.15 by default.
Not covered
Ampacity and cable derating (วสท. Tables 5-30 to 5-33), allowable tray load / span / deflection (YC has no published load table), seismic or fire-rating design, fittings, covers and accessories, and cable pulling or bending radius.
About YC Industrial
Y C INDUSTRIAL CO., LTD. manufactures cable trays – ladder, perforated and solid-bottom trough – in Rayong, Thailand. ISO 9001:2015.